G75-ADP | Analog differential pressure sensor
Operating temp: -10° to 60°C (no freezing)
Mechanical: Outdoor UV protection
Power supply: 5V DC
Mounting bracket: Optional
Mechanical
• Operating temperature : -10ºC to 60ºC
(no freezing)
• Outdoor UV protection
• Measuring pressure range : 0-7 bar (0-101.5 PSI)
• "H" proof pressure : 14 bar (203 PSI)
• "H" pressure must be ≥ "L" pressure
Electrical
• Power supply : 5V DC
• RED : (+) 5V
• BLACK : (-)5V
• ORANGE : analog output
• Analog output value :
0.2V to 4.7V, [V out = (0.006429xKpa+0.2)± Error]
• Ouput accuracy : 2.5% of full scale
Mounting
• 2" (52mm) diameter
• 2ft (60cm) 3 wires cable
• Pressure ports 1/8" BSP/NPT (male)
• High pressure port is marked by the letter "H"
on the housing
• Connect high pressure before low pressure
• Disconnect low pressure before high pressure
Standard protection class • IP66
联系人:彭工
手机:18918462396
电话:021-59718851
邮箱:kunage@126.com
地址: 上海市青浦区青浦工业园清河湾路819弄