About the installation and use of flexible rubber flexible joint

1 when the pipeline medium is acid-base, oil, high temperature and other special materials, the joint should be selected for one position above the working pressure of the pipeline.

2 when the pipe produces instantaneous pressure and greater than working pressure, it should select a joint which is higher than the working pressure. (for example, when the pipe starts at >1.0MPa for instantaneous pressure, the joint with work 1.6MPa shall be selected. For instantaneous pressure >1.6MPa, 2.5MPa connector should be used.

3 the rubber joint should be re pressurized and put into operation before the initial pressure is met, such as installation pressure test, etc., or after a longer shutdown.

4 the flange connecting the rubber joint shall be the valve flange or flange fitting GB/T9115.1 (RF).

5 high water or suspended water supply, the pipe should be fixed on the hanger, bracket or anchor, and can not allow the joint to bear the weight of the pipe and the axial force, otherwise the joint should be equipped with a pull off device (its bearing force must be greater than the axial force of the pipe).

6 the normal suitable medium for winding rubber joint is ordinary water at temperature of 0-60. If special medium such as oil, acid and alkali, high temperature and other corrosiveness and hard texture are hard, the rubber joint of special resistant material should be selected, which can not be used blindly or used in general.

7 flexure rubber joint use in the water pump import and export, should be located in the side of the water pump, and the water pump should be installed between the metal variable diameter joint, and installed in the large diameter of the diameter.

8 the suitable type must be selected according to the working pressure, connection mode, medium and compensation amount of the pipeline, and its quantity is selected according to the requirement of noise reduction and displacement.

9 when the displacement of the pipe is greater than the maximum compensation of the joint, the quantity of the joint should be increased to the parallel displacement. It is strictly forbidden to adjust the difference of the pipe, so that the joint is at the limit of the perturbed displacement and deviation state, and it can not exceed the limit degree (expansion, displacement, deflection and so on), and the concrete installation data is used to see the table.

10 when the rubber joint is installed, the screw bolts should be extended to the outside of the joint, and the bolts on each flange face are repeatedly tightened according to the method of diagonal compression to prevent the pressure deviation. The wire mouth joint should be tightened with the standard wrench. Do not use the force bar to force the sliding wire, slipping and fracture of the joint, and check regularly so as to avoid loosening or water seepage.

11 use or store rubber joints should avoid high temperature, ozone, oil and acid-base environment. A sun shading rack should be built for outdoor or sunny air facing pipes, and no exposure to sunlight, rain or wind erosion. The surface of the joint is strictly prohibited by painting and winding insulation. Due to the aging problem of rubber products, they should be checked and replaced in time.