Introduction of the fault and elimination of the solenoid valve
Welcome: KUNAG Fluid Control System (Shanghai) Co., Ltd.
Language: Chinese ∷  English
Search

News

Introduction of the fault and elimination of the solenoid valve

1. The solenoid valve does not work after it is electrified

Check whether power wiring is bad, re wiring and connector connection.

Check whether the supply voltage is within the range of + - to normal location.

Whether or not the coils are removed and re welded

Coils short circuiting and changing coils

Is the working pressure difference inappropriate? Adjust the differential pressure to replace the equivalent solenoid valve.

The fluid temperature is too high to replace the proportionate solenoid valve

Impurities cause the main spool and moving iron core of the solenoid valve to be stuck and cleaned. If seal damage occurs, replace the seal and install the filter.

The viscosity of the liquid is too high, the frequency is too high, and the life has arrived.

Two, the solenoid valve can not be shut down

Seal of main spool or iron core has been damaged. Replace seal.

If the fluid temperature and viscosity are too high, replace the counterpart solenoid valves.

The impurity enters the electromagnetic valve to produce the valve core or the moving iron core.

Spring life has been or deformed

Blockage of the balance hole of the throttle hole - cleaning in time

Working frequency is too high or life expectancy has changed.

Three. Other cases

Internal leakage to check whether the seal is damaged, and whether the spring is assembled badly.

Leakage: connect loosening or seal is broken. Tighten screws or replace seals.

There is noise when power is switched on, and the fastener on the head is loose and tightened. Voltage fluctuation is not within the allowable range, adjust the voltage. Clean or replace the impurities or uneven surfaces of the core.