Electromagnetic flowmeter installation location selection instructions
The choice of electromagnetic flow
meter installation location:
In order to make the
transmitter work stably, the electromagnetic flow
meter should pay attention to the following requirements when selecting the installation location:
1) Try to avoid ferromagnetic objects and equipment with strong electromagnetic fields (such as large motors, large transformers, etc.) to prevent the magnetic field from affecting the working magnetic field and flow information of the
sensor.
2) It should be installed in a dry and ventilated place as much as possible. It should not be installed in a place with damp or water accumulation.
3) Try to avoid sun and rain, avoid ambient temperature above 45 ° C and relative humidity greater than 95%
4) Choose a place that is convenient for maintenance and convenient for activities
5) The flow
meter should be installed at the rear end of the
pump and must never be installed on the suction side; the valve should be installed on the downstream side of the flow
meter.