Introduction to the selection of vortex flowmeter
Selection of vortex flow
meter
1 vortex flow
transmitter selection
Our company adopts VA type piezoelectric vortex flow
transmitter produced by ABG instrument in saturated steam measurement. Because of the wide range of vortex flow
meter, in practical applications, it is generally considered that the flow of saturated steam should not be low. The lower limit of the vortex flow
meter, that is, the fluid flow rate must not be less than 5m/s. The vortex flow
transmitters of different calibers are selected according to the amount of steam used, and the caliber of the
transmitter cannot be selected by the existing process pipe dia
meter.
2 pressure compensation pressure
transmitter selection
Since the saturated steam line is long and the pressure fluctuates greatly, pressure compensation must be adopted. Considering the corresponding relationship of pressure, temperature and density, only pressure compensation can be used in the measurement, because the saturated steam pressure of our company is in the range of 0.3-0.7MPa. The range of the pressure
transmitter can be selected as 1 MPa.
3 display instrument selection
Display instrument intelligent flow display instrument with temperature and pressure compensation, instantaneous flow display and cumulative flow accumulation.