HONEYWELL explosion-proof switch acceptance requirements introduction
Welcome: KUNAG Fluid Control System (Shanghai) Co., Ltd.
Language: Chinese ∷  English
Search

brand information

HONEYWELL explosion-proof switch acceptance requirements introduction

Honeywell HONEYWELL explosion-proof switch acceptance requirements

1. The shell has no deformation, no welding, no rust, no serious deformation of the bracket
2. The operation handle is in the correct position, the toggle is flexible, and the operation shaft is firmly connected, no virtual action
3. The contact of the vacuum contactor is good, the parts in the arc extinguishing chamber are free from oxidative discoloration, the vacuum degree is in compliance with the regulations, and there is no serious discharge trace.
4. Good contact, the insertion depth is not less than 2/3 of the width of the blade, and the contact area is not less than 75 [%] of the holder.
5. The opening and closing position of the movable knife gate, the action direction is strictly consistent with the handle.

HONEYWELL explosion-proof switch technical parameters Power supply voltage: DC 24V or AC 220V Operating temperature: Switch body -40 ~ 150 °C; Instrument -30 ~ 70 °C Working pressure: Less than 2MPa Medium density: Minimum 0.7g / cm3 Output mode: Output (AC220V / 3A, DC 30V/3A) Output delay: 1~20 seconds adjustable explosion-proof mark: dIIBT4 Power consumption: 1W Mounting connector: R1 Electrical interface: M20×1.5

Honeywell HONEYWELL Explosion-Proof Switch Application Range Explosion-proof switches are used in a variety of applications that require a safe, reliable, and easily disconnected connection. Especially in the manufacturing equipment and system power supply where explosive gas may exist; also used in the petrochemical industry; including mills, granaries, paint or ink manufacturers, wood processing plants, cement plants, shipping and sewage treatment. HONEYWELL explosion-proof switches are also suitable for use in external electrical equipment such as motors, pumps, lighting equipment, process control devices used in hazardous manufacturers and factories, or in explosive atmospheres that cause flammable gases, steam, mist or flammable dust.