Solenoid valve coil introduction
About this solenoid valve
coil
There are many kinds of solenoid valves, such as gas control, liquid (such as oil, water), most of which are
coiled on the valve body, can be separated, the valve core is made of ferromagnetic material, which is generated when the
coil is energized. The magnetically actuated spool is actuated by the spool to open or close the valve. The
coil can be taken separately. This solenoid valve is used to control the opening or closing of the gas pipeline. The movable iron core in the solenoid valve
coil is attracted and moved by the
coil when the valve is energized, and drives the spool to move to change the conduction state of the valve.
First, the cause of the solenoid valve
coil heating
When the
coil of the solenoid valve is in the working state (energized), the core is attracted to form a closed magnetic circuit. That is, when the inductance is at the maximum state, the design time. The heat is normal, but the core can not be smoothly sucked when the core is energized, the inductance of the
coil is reduced, the impedance is reduced, and the current is increased accordingly. This causes the
coil current to be too large and the life is affected, so the oil, impurities, deformation, etc. hinder the iron core activity. When the power is turned on, the action is slow, and even if it is not normally fully absorbed, the
coil is often energized with a state in which the impedance is less than normal, which is a factor that causes the
coil to heat up.
Second, the quality of the solenoid valve
coil is confirmed
Use a multi
meter to measure the resistance of the solenoid valve. The resistance of the
coil should be around 1K ohm! If the resistance of the
coil is infinite, it means an open circuit. If the
coil resistance tends to zero, it means a short circuit, it should be replaced with a new one.
Third, the electromagnetic valve
coil magnetic force is related to what
The magnetic force of the solenoid valve
coil is related to the wire dia
meter and the number of turns of the
coil and the magnetic conductive area of the magnetic steel, that is, the magnetic flux. The DC electromagnetic
coil can be pulled out from the iron core; if the AC is not available, the AC
coil is pulled out from the iron core, which will cause the
coil current to surge and burn the
coil. There is a shorting ring inside the AC
coil core to reduce vibration. A short circuit ring is not required inside the DC
coil core.
Fourth, solenoid valve
coil price
The wholesale price on the market is not fixed. The price of the
coils of the solenoid valves used by different manufacturers and different product models will vary. There are more than a dozen cheaper ones, 50-80 yuan in the middle, and 100 in the good ones. More than 100 prices.
Five, the problem of the solenoid valve
coil:
Q: Recently, the solid
coil of the solenoid valve has broken down. The resistance of the normal
coil is about 1~2100 ohms, and there is an open circuit when it is broken. I don't know why the solenoid valve
coil is broken. It is reasonable to say that the solid
coil should not be broken easily. Some say it is the reason for the power supply (just use 220VAC mains without UPS uninterruptible power supply). The TG2531-10M two-position five-way solenoid valve power supply is DC24V, and the 24V power supply is converted by the uninterruptible power supply 220VAC into the switching power supply. It’s hard to be true that the power supply can be converted to 220VAC by the mains. What is the reason??
A: The main reason I think is as follows: The
coil is damp, causing poor insulation and magnetic leakage, causing the current in the
coil to be too large and burned, so it is necessary to prevent rainwater from entering the solenoid valve (my unit has recently broken a few, it is this Cause) In addition, the spring is too hard, the reaction force is too large, the number of
coil turns is too small, the suction is not enough, the
coil can be burnt, and the power supply will not be a problem under normal conditions. If the power supply fails, the bad one is a batch, not one. One.
Q: I bought an air compressor automatic drain valve. Now I have added a contactor. I have an auxiliary switch on the contactor. When I turn on the machine, the automatic drainer discharges water for ten seconds every fifteen minutes. The air compressor power contactor releases the auxiliary switch and connects to another set of power supply to continuously supply power to the solenoid valve of the automatic drainer, so that the air in the air compressor can be completely discharged after the shutdown, the effect is good, now the problem It is the solenoid valve
coil has been burned two, indicating that the solenoid valve
coil can not be energized for a long time, I would like to ask you any way to solve?
A: A freewheeling diode is connected to the
coil of the solenoid valve to reduce the effect of current shock on the
coil. Or choose the rated current of the solenoid valve to be larger.