Solenoid valve coil common four kinds of faults and solutions
What are the main faults of pneumatic solenoid valves, and how to solve them. The failure of the pneumatic solenoid valve will directly affect the action of the switching valve and the regulating valve. The common faults have solenoid valves that do not operate. The following aspects should be investigated: The following four aspects are mainly introduced.
1. The solenoid valve
coil is burnt out. The wiring of the solenoid valve can be removed and measured with a multi
meter. If the circuit is open, the solenoid valve
coil is burnt out. The reason is that the
coil is damp, causing poor insulation and magnetic leakage, causing the current in the
coil to be too large and burning, so it is necessary to prevent rainwater from entering the solenoid valve. In addition, the spring is too hard, the reaction force is too large, the number of turns of the
coil is too small, and the suction force is insufficient to cause the
coil to burn. In emergency processing, the manual button on the
coil can be turned from the “0” position to the “1” position during normal operation, so that the valve is opened.
2, leaking gas. Leakage can cause insufficient air pressure, making it difficult to open and close the forced valve due to damage to the gasket or wear of the spool to cause several cavity helium. When dealing with the solenoid valve failure of the switching system, the appropriate timing should be selected, and the solenoid valve should be processed when the power is lost. If the processing is not completed within one switching gap, the switching system can be suspended and taken care of.
3. The solenoid valve is stuck. The clearance between the sliding valve sleeve of the solenoid valve and the valve core is very small (less than 0.008 mm), and it is generally a one-piece assembly. When mechanical impurities are introduced or the lubricating oil is too small, it is easy to get stuck. The treatment method can use the steel wire to break in from the small hole of the head to make it bounce back. The fundamental solution is to remove the solenoid valve, take out the valve core and the valve core sleeve, and clean it with CCI4, so that the valve core can move flexibly in the valve sleeve. When disassembling, pay attention to the assembly sequence and external wiring position of each component, so as to reassemble and wire correctly, and check whether the oil mist injection hole is blocked and the lubricating oil is sufficient.
4. The solenoid valve terminal is loose or the wire ends are off. The solenoid valve is not allowed to be energized and the wire ends can be tightened.